Select when performing continuous digital output (Generating)
DoClockType |
[-1]can be set |
Initial value: 1 (Internal clock) |
Specify the type of clock (Internal clock/External clock/Synchronization control signal)
1:
Internal clock
2: External clock
3: Handshake
4: Synchronous Control Signal1
5: Synchronous Control Signal2
6: Synchronous Control Signal3
* In synchronous operation, it is the slave
device that selects the synchronization control signal for the clock
* The recommended setting when synchronization control signal is used for
clock is Synchronous Control Signal 1
DoGeneratingClock |
[-1]can be set |
Initial value: 1 : 2 |
Specify the internal clock speed with a two-element
cluster
It is unnecessary to set when using a clock other than the internal clock
- Element 1: Clock value(Clock)
Specify the clock value
It can be set within the following range in combination with clock value
unit (Unit)
- For DIO-32DM3-PE
20 nanoseconds <= clock="" <="21" seconds="" (5="" nanoseconds="" unit)
- For PIO-32DM(PCI), DIO-32DM2-PE
50 nanoseconds <= clock="" <="107" seconds="" (25="" nanoseconds="" unit)
- Element 2: Clock value unit(Unit)
Specify the unit of the clock value
1:
1sec unit
2: 1ms unit
3: 1us unit
4: 1ns unit