Wireless I/O Specifications

This page explains the specification of wireless I/O.

Wireless I/O configuration

The basic configuration when using wireless I/O products is as follows.

Personal computer --- Ethernet --- Gateway (Master unit) --- 920 MHz --- Terminal (Slave unit)

How to acquire data from a personal computer

The following two methods are available for acquiring data from a personal computer.

Acquire data stored in the parent machine
The flow acquiring the data stored in the master unit is as follows.


1.Send an instruction to retrieve the saved data from the PC to the gateway.
2.The gateway sends its own data to the PC.

Apart from the above flow, the slave unit periodically transmits data to the master unit.

The data saved by the master unit is updated when data is received from the slave unit.

The interval at which the slave unit transmits data to the master unit can be changed by setting the slave unit.

Please change the setting with CONTEC Device Utility.

Acquire data stored in slave unit
The flow acquiring the data stored in the slave unit is as follows.


1.Send an instruction to retrieve the slave unit data from the PC to the master unit.
2.The master unit requests data from the slave unit.
3.The slave unit sends the current data to the master unit.
4.The master unit transmits the data acquired from the slave unit to the PC.

Features of 920 MHz

When communicating at 920 MHz, the transmission time is restricted by the transmission output/channel.
Please refer to the table below for transmission time limit.

Transmission output

Channel No.

Transmission time

Limit

Pause time after one transmission

Max. sum total limit of transmission time per hour

1mW

1 to 5

100ms less

100ms

3.5s

1mW to 20mW

62 to 77

50ms less

50ms

No limit

33 to 61

200ms over 400ms less

10 times the transmission time

360s

6ms over 200ms less

2ms

6ms less

No limit

As there is a limit on 920 MHz, please be careful when accessing the slave unit from the PC continuously when acquiring data of the slave unit.
When acquiring the saved data from the PC to the master unit, since there is no access to the slave unit, the limit of 920 MHz is not a problem.
However, please note that the data stored in the master unit is not real time information of the slave unit.