Retrieves the generated count of the analog output.
Ret = AioGetAoSamplingCount ( ID , AoSamplingCount )
Id
[ VB.NET : Short ] [ C, C++ : short ] [ C# : short ] [ Python : ctypes.c_short
]
Specifies the ID retrieved from AioInit function.
AoSamplingCount
[ VB.NET : Integer ] [ C, C++ : long * ] [ C# : out int ] [ Python : ctypes.POINTER(ctypes.c_long)
]
Specifies the address of the variable that stores the generating count.
Ret [ VB.NET : Integer ] [ C, C++ : long ] [ C# : int ] [ Python : ctypes.c_long ]
Return values |
Content |
0 |
Normality completion |
7 |
Execute AioResetDevice function because the device has recovered from standby mode |
10001 |
Invalid
Id was specified |
10002 |
AIO
driver can't be called |
13400 |
Pointer
to AoSamplingCount is NULL |
20001 |
This function can't be used by this device |
20003 |
Can
not use because another process is using the device |
In all devices, AoSamplingCount = 0
You can retrieve the generated count of the
analog output feature.
You may also refer this number as indicating the index of device buffer.
Resets this value to 0 by calling AioResetAoMemory function.
Stores the generating counts of all channels
used in the AioStartAo.
This function can be executed even if the device is in operation.
This function cannot be used on devices without the analog output function.
Please use the AioGetAoSamplingTimes function when you need the remain numbers of generating on device buffer.
For example, you specify 2000 data for device
buffer and your device has already generated 500 data out of 2000 data.
You may have the following number with 2nd argument of each functions at
that time.
AioGetAoSamplingCounts : AoSamplingCount
= 500
AioGetAoSamplingTimes : AoSamplingTimes = 1500
Retrieves the generating count (location) from the device memory (software memory).
VB.NET |
Dim
Ret As Integer |
C, C++ |
long
Ret; |
C# |
int
Ret; |
Python |
Ret
= ctypes.c_long() |